EasyDC-FOS presents its passive fibre-optic partial discharge monitoring system at the V Edition of FutuRed Smart Power Grids Congress
Madrid, 3-4 November 2026
EasyDC-FOS took part in the V Smart Grids Congress (V Congreso de Redes Eléctricas), held on 3 and 4 November at the School of Industrial Engineering of the Universidad Politécnica de Madrid. The congress is organised by ITE (Instituto Tecnológico de la Energía) in collaboration with FutuRed, the Spanish Smart Grids Technology Platform. Each year it brings together distribution system operators, manufacturers, technology companies, research centres and universities to share progress and real-world experience on the main challenges facing the power sector.
Lander Merino, SW Leader HVDC at RDT Lumiker, the project coordinator, presented a poster of the technical paper “Passive Fibre-Optic Monitoring System for Partial Discharge Detection in Long High-Voltage Cables”.
Monitoring partial discharges in long high-voltage cables requires measurement points distributed along the link, at joints, terminations and grounding points. Conventional solutions need powered electronics, power supply and communications at each of these locations. The architecture developed in EasyDC-FOS keeps the remote sensing points completely passive. The signals captured by HFCT sensors are sent through optical fibre to an interrogator and to centralised acquisition and diagnostic equipment.
The paper describes how the system has evolved from a first two-fibre prototype, which validated the complete measurement chain, to a new four-fibre architecture. The new prototype achieves a significant gain in sensitivity, with partial discharge waveforms clearly distinguishable from around 5 pC under direct injection. It also performed stably after adding 16 km of optical fibre. The next steps will focus on validating the prototype under conditions representative of high-voltage cables and integrating it with partial discharge diagnostic tools.
The work was carried out with contributions from Ampacimon in partial discharge acquisition and analysis, and from the Universidad Politécnica de Madrid, which provided the HV cable mock-up used in the preliminary tests.
The full paper is available in the congress proceedings (page 228): https://lnkd.in/eRGXn3vZ